PART 1 - GENERAL
1.01 Description
A. The information herein details a low profile
resilient mechanically fastened nailed system
comprised of a continuous steel channel wrapped
around hardwood plywood with resilient natural
rubber pads, adjusta-flex foam underlayment, a
layer of 15/32" exposure 1 sheathing and finish
flooring.
B. The flooring system assembled shall meet DIN
18032 Part 2: 1991.
C. The general contractor shall provide a level
slab, steel troweled to a tolerance of plus or
minus 1/8" in a 10'0" radius and subject to the
approval of the wood floor contractor. Moisture
barriers must be adequate for conditions. The
concrete slab is to be depressed
1-3/8" plus the thickness of the flooring
specified.
1.02 Quality Assurance
A. All system component parts must be supplied
by Action Floor Systems, LLC.
B. The Flooring contractor must be approved by
Action Floor Systems, LLC.
C. Flooring materials must be allowed to
acclimate to building conditions on the job site
in a dry, well-ventilated area, not in contact
with masonry, and shall be installed at a
moisture content not to exceed 8% except in
areas of constant high humidity where the
moisture content of the flooring shall not
exceed 10%.
1.03 Working Conditions
A. The wood flooring shall not be installed
until all masonry, plastering, tile, marble, and
terrazzo work is completed, and overhead
mechanical trades and painters have finished in
wood floor area. The building must be reasonably
dry; all openings must be closed in; permanent
heating, ventilating and air conditioning
installed and operating before, during and after
installation.
B. The concrete slab shall be dry, free of
foreign materials, and turned over to the wood
floor contractor broom clean. Moderate room
temperature of 65 degrees or more shall be
maintained a week preceding and throughout the
duration of the work. Humidity conditions within
the building shall approximate humidity
conditions which will prevail when the building
is occupied. If prior experience indicates
relative humidity during sustained heating
periods will fall below 35%, building
engineering shall introduce moisture into the
area when required. Conversely, if relative
humidity increases to 50% or higher, measures
should be taken to bring the relative humidity
back under control. This may require turning on
the heat.
1.04 Warranty
A. Action Floor Systems, LLC. warrants the
material it ships to be free from defects in
materials and workmanship for a period of one
year and the flooring installer warrants the
installation of the flooring to be free of
defects in materials and workmanship for a
period of one year. The exclusive remedy under
this warranty shall be replacement of defective
material supplied by Action Floor Systems, LLC.,
or correction of defective installation by the
flooring installer. All implied warranties of
merchantability or fitness for intended use are
limited to the period of this warranty. This
warranty excludes consequential damages.
B. This warranty does not cover damage caused by
fire, winds, floods, chemicals or other abuse,
or by failure of other contractors to adhere to
specifications, or neglect of reasonable
precaution to provide adequate ventilation
during hot and humid weather. This warranty also
excludes damage due to excessive dryness or
excessive moisture from humidity, spillage,
migration through the slab or wall or any other
source. This warranty also excludes damage to
floors due to ordinary wear and tear, faulty
construction of the building (other than the
flooring installation), separation of the
concrete slab, underlying the floor, settlement
of walls, or use of water on the floors.
C. During period of the warranty, the floor
cannot be coated without the approval of the
flooring contractor.
PART 2 - PRODUCTS
2.01 Materials
A. Flooring
1. Flooring shall be 25/32" x 2-1/4", 2nd & Btr.
northern hard maple, TGEM, MFMA grade marked as
manufactured by Action Floor Systems, LLC.
2. OPTIONS:
a. Sizes 25/32" x 1-1/2", 33/32" x 2-1/4" or
1-1/2".
b. Grades, 1st, 3rd & Btr. and 3rd.
c. Action Long-Length strip.
d. Wood flooring shall be treated by Action with
Woodlife F when specified.
B. Subfloor
1. Vapor barrier shall be 6-mil polyethylene
2. Adjusta-flex underlayment shall be 1"
closed-cell multicellular flexible foam and have
a density of 1.7 - 2.3 PCF.
3. Channels shall be steel encased hardwood
plywood with alternating "T" slots and reflex
slots. Pneumatic deflection force limiters of
natural rubber shall be attached per Action
Floor specifications.
4. Channel anchoring retainers shall be 16 gauge
steel.
5. Channel anchoring pins shall be 1-1/4" long
hardened steel.
6. Plywood shall be 15/32" exposure 1 sheathing.
7. Flooring fasteners shall be 1-1/2" cleats or
1-1/2" coated staples.
8. Wall base shall be 4" x 3" vented cove base
with premolded outside corners (specify black or
brown), as supplied by Action.
PART 3 - EXECUTION
3.01 Inspection
A. Inspect concrete slab or proper tolerance and
dryness, reporting in writing any discrepancies
to the general contractor.
B. All work required to put the concrete slab in
acceptable condition shall be the responsibility
of the general contractor.
C. The slab shall be broom cleaned by the
general contractor.
3.02 Installation
A. Cover concrete slab with poly, lapping edges
6" and seal with adhesive or 2" duct tape.
B. Place channels 12" on center across the short
dimension of the area. Stagger ends of channels
in adjacent rows.
C. Channel Anchoring retainers shall be attached
to concrete with steel drive pins.
D. Lay out adjusta-flex foam between channels.
E. Lay plywood sheathing perpendicular to
intended direction of the finish flooring,
gluing and nailing plywood to channels. Use
plywood clips to support any unsupported ends.
F. Machine fasten strip flooring through plywood
into channel at each intersection. End joints
must be properly driven up and proper spacing
provided for the humidity conditions of the area
as recommended by the local Action Flooring
Systems, LLC. flooring contractor. Allow 2"
expansion voids at perimeters and all vertical
obstructions.
3.03 Floor Sanding
A. Use coarse, medium, and fine grade sandpaper.
B. After sanding, buff entire floor using 100
grit screen or equal grit sandpaper with a
heavy-duty buffing machine.
C. Vacuum or tack floor before first coat of
seal.
D. Floor shall present a smooth surface without
drum stop marks, gouges, streaks, or shiners.
3.04 Finishing
A. Inspect entire area of floor to ensure the
surface is acceptable for finishing, completely
free from sanding dust, and perfectly clean.
B. Apply seal and finish per manufacturer's
instructions.
C. Buff and vacuum or tack between each coat
after it dries.
D. Apply game lines accurately after the seal
coat, after buffing and vacuuming. Lay out in
accordance with drawings. For game lines, use
current rules of association having
jurisdiction. Lines shall be straight with sharp
edges in colors selected by the architect. Game
line paint shall be compatible with finish.
3.05 Base Installation
A. Affix rubber vent base to wall with
recommended adhesive or screws. Miter all inside
corners carefully. Use premolded outside
corners.
3.06 Clean up
A. Clean up all unused materials and debris and
remove.
3.07 Maintenance
A. Upon completion of floor installation, the
owners, attendants or individuals in charge and
responsible for the upkeep of the building are
to see the care and maintenance instructions of
the Maple Flooring Manufacturers Associationn
are followed. Failure to follow care and
maintenance guidelines may void warranty.